Government Contract | Florida
Sebring High Replacement Chiller

Bid Information

Bid Alert No: 00000480798

Bid Title: Sebring High Replacement Chiller

Agency Bid No. Title: SBHC1516_05

Received Date: 02/08/2016

Close Date: 02/24/2016

Purchase Type: Not Stated

Delivery Point:

Delivery Date: Not Stated

Special Notices: Warranty Required


Specifications include, but are not limited to:Furnish, and Commission factory assembled, charged, and operational runtested air-cooled screw compressor chiller as specified herein. Chiller shall include, but isnot limited to: a complete system with multiple independent refrigerant circuits, semi 'hermetic twin screw compressors, shell and tube hybrid falling film type evaporator, aircooledcondenser, R134a or 410a refrigerant,lubrication system, interconnecfing wiring,safety and operating controls including capacity controller, control center, motor startingcomponents, and special features as specified herein or required for safe, automaticoperation.b. Efficiency: Chiller submittal shall have:1) Scheduled minimum efficiency @ AHRI conditions, required for Duke Energyrebatec. Unit Cabinet:1) Frame shall be of heavy-gage galvanized steel.2) Cabinet shall be galvanized steel casing with a pre-painted finish.3) Cabinet shall be capable of withstanding 1000-hour salt spray test in accordancewith the ASTM(U.S.A.) B-117 standardd. Fans:1) Condenser fans shall be ultra-quiet, low RPM direct-driven, airfoil cross-sectionblade, reinforced polymer construction, shrouded-axial type, and shall be staticallyand dynamically balanced with inherent corrosion resistance. Air shall bedischarged vertically upward.2) Fans shall be protected by coated steel wire safety guards.e. Compressors ,1) Compressors: Shall be VSD direct drive, semi hermetic, rotary twin-screw type,including: muffler, temperature actuated 'off-cycle' heater, rain-tight terminalbox, discharge shut-off service valve, suction shut-off service valve for each .compressor, and precision machined cast iron housing. Design working pressure ofentire compressor, suction to discharge, Shall be 350 psig (24 barg) or higher.Compressor shall be U.L Recognized.2) Each compressor shall be equipped with a discharge shutoff valve. .3) Each compressor shall have crankcase heaters installed and properly sized tominimize the amount of liquid refrigerant present in the oil sump during off cycle.

Bid Related Documents

Download Document

Product Codes: 91450, 91468

Agency Information

Issuing Agency: Highlands County School District

State: Florida

Agency Type: State and Local

Contact: Shawn Stamps Administration Building, 426 School Street, Sebring, Florida, 33870

Phone: 863-471-5645

Fax: 863-471-5650




FREE Market Analysis